Sponsored Links

Minggu, 29 Oktober 2017

Sponsored Links
Toronto's Deep Lake Water Cooling System - Buildipedia

Deep water source cooling (DWSC) or deep water air cooling is a form of air cooling for process and comfort space cooling which uses a large body of naturally cold water as a heat sink. It uses water at 4 to 10 degrees Celsius drawn from deep areas within lakes, oceans, aquifers or rivers, which is pumped through the one side of a heat exchanger. On the other side of the heat exchanger, cooled water is produced.


Video Deep water source cooling



Basic concept

Water is most dense at 3.98 °C (39.16 °F) at standard atmospheric pressure. Thus as water cools below 3.98 °C it decreases in density and will rise. As the temperature climbs above 3.98 °C, water density also decreases and causes the water to rise, which is why lakes are warmer on the surface during the summer. The combination of these two effects means that the bottom of most deep bodies of water located well away from the equatorial regions is at a constant 3.98 °C.

Air conditioners are heat pumps. During the summer, when outside air temperatures are higher than the temperature inside a building, air conditioners use electricity to transfer heat from the cooler interior of the building to the warmer exterior ambient. This process uses electrical energy.

Unlike residential air conditioners, most modern commercial air conditioning systems do not transfer heat directly into the exterior air. The thermodynamic efficiency of the overall system can be improved by utilizing evaporative cooling, where the temperature of the cooling water is lowered close to the wet-bulb temperature by evaporation in a cooling tower. This cooled water then acts as the heat sink for the heat pump.

Deep lake water cooling uses cold water pumped from the bottom of a lake as a heat sink for climate control systems. Because heat pump efficiency improves as the heat sink gets colder, deep lake water cooling can reduce the electrical demands of large cooling systems where it is available. It is similar in concept to modern geothermal sinks, but generally simpler to construct given a suitable water source.

Deep lake water cooling allows higher thermodynamic efficiency by using cold deep lake water, which is colder than the ambient wet bulb temperature. The higher efficiency results in less electricity used. For many buildings, the lake water is sufficiently cold that the refrigeration portion of the air conditioning systems can be shut down during some environmental conditions and the building interior heat can be transferred directly to the lake water heat sink. This is referred to as "free cooling", but is not actually free, since pumps and fans run to circulate the lake water and building air.

One added attraction of deep lake water cooling is that it saves energy during peak load times, such as summer afternoons, when a sizable amount of the total electrical grid load is air conditioning.


Maps Deep water source cooling



Advantages

Deep water source cooling is very energy efficient, requiring only 1/10 of the average energy required by conventional cooler systems. Consequently, its running costs can also be expected to be much lower.

The energy source is very local and fully renewable, provided that the water and heat rejected into the environment (often the same lake or a nearby river) does not disturb the natural cycles. It does not use any ozone depleting refrigerant.

Depending on the needs and on the water temperature, couple heating and cooling can be considered. For example, heat could first be extracted from the water (making it colder); and, secondly, that same water could cycle to a refrigerating unit to be used for even more effective cold production.


Performance Analysis of Automated Control System for Condenser ...


Disadvantages

Deep water source cooling requires a large and deep water quantity in the surroundings. To obtain water in the 3 to 6 °C (37 to 43 °F) range, a depth of 50 m (160 ft) to 70 m (230 ft) is generally required, depending on the local conditions.

The set-up of a system is expensive and labour-intensive. The system also requires a great amount of source material for its construction and placement.


LAKE-SOURCE COOLING


First major system in the United States

Cornell University's Lake Source Cooling System uses Cayuga Lake as a heat sink to operate the central chilled water system for its campus and to also provide cooling to the Ithaca City School District. The system has operated since the summer of 2000 and was built at a cost of $55â€"60 million. It cools a 14,500 ton (51 megawatt) load.


Toronto's Deep Lake Water Cooling System - Buildipedia


First system in Canada

Since August 2004, a deep lake water cooling system has been operated by the Enwave Energy Corporation in Toronto, Ontario. It draws water from Lake Ontario through tubes extending 5 kilometres (3.1 mi) into the lake, reaching to a depth of 83 metres (272 ft). The deep lake water cooling system is part of an integrated district cooling system that covers Toronto's financial district, and has a cooling power of 59,000 tons (207 MW). The system currently has enough capacity to cool 3,200,000 square metres (34,000,000 sq ft) of office space.

The cold water drawn from Lake Ontario's deep layer in the Enwave system is not returned directly to the lake once it has been run through the heat exchange system. The Enwave system only uses water that is destined to meet the city's domestic water needs. Therefore, the Enwave system does not pollute the lake with a plume of waste heat.


Southeastern Atlantic deep-water evolution during the late-middle ...


Seawater air conditioning

Also known as Ocean Water Cooling. The InterContinental Resort and Thalasso-Spa on the island of Bora Bora uses a seawater air conditioning (SWAC) system to air-condition its buildings. The system accomplishes this by passing cold seawater through a heat exchanger where it cools freshwater in a closed loop system. This cool freshwater is then pumped to buildings and is used for cooling directly (no conversion to electricity takes place). Similar systems are also in place in The Excelsior hotel and The Hong Kong and Shanghai Banking Corporation main building in Hong Kong, and at the Natural Energy Laboratory of Hawaii Authority. The InterContinental Resort is the largest seawater air conditioning system to date, though there are several other, larger systems being planned. Honolulu Seawater Air Conditioning is a project intending to use seawater air conditioning to deliver renewable cooling to commercial and residential properties in the downtown Honolulu area. It is majority owned by eBay founder Pierre Omidyar's Ulupono Initiative.


File:Deep water air cooling (pond).JPG - Wikimedia Commons


See also

  • District heating
  • Free cooling
  • Geothermal heat pump
  • Seasonal thermal energy storage (STES)
  • Solar pond
  • Ocean energy
  • Ocean thermal energy conversion

Southeastern Atlantic deep-water evolution during the late-middle ...


Notes


One of the Largest IPP Power Plants in the Middle East Uses ...


References

  • Sudick, Jennifer. "New seawater cooling plant in the works". Honolulu Star-Bulletin. Vol. 13, Issue 15 - Tuesday, January 15, 2008. Retrieved 2008-04-26. 
  • Long Beach Press-Telegram , April 7, 2005, USING COLD SEAWATER FOR AIR-CONDITIONING



External links

  • From Lake Depths, a Blast of Cool for Consumers
  • Cornell University Lake Source Cooling overview and details of how it works
  • Geocean has performed the design and installation of a SWAC system for the Brando Hotel in French Polynesia.
  • Makai Ocean Engineering has designed SWAC systems in Bora Bora (installed), Kona (installed) and Honolulu, Hawaii, la Reunion, Curaçao, Bahamas, and DWSC systems at Cornell University and Toronto (both installed).
Comments
0 Comments